Flame arrester series
Products
HomeProductsFlame arrester seriesPipeline vent flame arrester

Pipeline vent flame arrester

The pipeline vent flame arrester is used to install the fixed roof storage tank of crude oil, gasoline, kerosene, diesel, aromatics, sulfur and other oil products or other chemical materials. It is usually used together with the breather valve. Its main function is to allow flammable and explosive gases to pass through and prevent suffocation of the flame introduced into the storage tank, The flame arrester was jointly designed and manufactured by Beijing Design Institute and Fushun Petroleum Machinery Factory in 1985. It was tested by Tianjin Fire Science Research Institute of the Ministry of public security and met the provisions of the national standard gb5908-86 of the people's Republic of China. All technical indexes meet the requirements of inspection standards and can be used under low temperature conditions in alpine areas. The pipe flame arrester can be matched with the vent pipe or used alone. Products of other specifications can be provided according to user requirements


Consult Now
Business Card 联系方式

Scope of application

The flame arrester is suitable for storing class a oil products with a flash point lower than 28 ℃ and class B oil products with a flash point lower than 60 ℃. It is also suitable for storing materials on the dome roof tank capped with nitrogen. The principle of gravel flame arrester and mesh flame arrester is the same as above. It can be used in combination with breather valve and breather inlet hole, or it can be used alone

Technical requirements

1. The explosion resistance performance is qualified, and the fire can be stopped every time after 13 consecutive tests
2. Qualified fire resistance, fire resistance, no tempering for 1 hour
3. The flame arrester shall be inspected once every six months to check whether the core of the flame retardant layer is blocked, deformed, corroded, etc
4. If the blocked fire retardant layer is found, the core shall be cleaned to ensure that each hole on the core is unblocked, and the deformed and corroded fire retardant layer shall be replaced
5. When reinstalling the fire barrier core, ensure that the joint surface is tight without air leakage

Performance parameters

Product Model
LTLZH-6
connection form
Flange
nominal diameter
DN50~DN200(mm)
applicable media
Water, oil, steam, corrosive liquid
pressure range
0.6~4.0MPa
applicable temperature
& le; 450℃

Connecting dimension of pipe flame arrester

Product Code
nominal diameter of nozzle DN
structure size (mm)
remarks
A
B
C
D
LZLZH-6-01
50
150
175
260
185
pipe flange standard hg20594 (also according to user requirements)
LZLZH-6-02
80
185
240
320
215
LZLZH-6-03
100
250
300
380
270
LZLZH-6-04
150
300
425
470
320
LZLZH-6-05
200
350
520
550
370
material
shell
flame retardant core
cast steel
stainless steel corrugated plate
safe fire suppression speed
V=2300m/s
limit fire retardant speed
V=1400m/s