The flame retardant corrugated plate is usually made of stainless steel strip or copper nickel alloy. The size of the ripple is determined by the nature of the gas and the speed of stopping the flame. There are two forms of corrugated fire layer: one is composed of corrugated sheet materials folded in two directions, and the corrugations are separated into many small pores and channels, providing a tortuous channel for the flame. The other is that the corrugated thin plate and flat plate are alternately wound on the central axis to form a stack of fire retardant layers with triangular pores. The fire retardant layer of this structure can produce corrugated fire retardant layers with different diameters, thicknesses and pores according to the design needs
The thickness of common corrugated sheet is 0.1 ~ 0.3mm, and the height of corrugated sheet is generally 0.2mm, 0.3mm, 0.5mm and 0.7mm
And 1.2mm, etc., shall be determined according to the flame stopping speed
The flame arrester with corrugated structure has been tested and proved to have the advantages of good flame retardant performance, wide application range, low manufacturing cost, easy inspection and installation, so the flame arrester with this structure has been widely used
The corrugated structure flame retardant layer can be composed of several flame retardant layers as a whole, but no gap is allowed between layers to prevent the flame from passing through the gap and destroy the overall flame retardant performance of the flame arrester
A. The flame arrester shell can be made of cast iron, aluminum alloy, cast steel and stainless steel according to the service medium
B. The casting size of the shell must meet the specified requirements
C. The shell casting shall be free of cracks, shrinkage cavities, sand holes, damages and other defects to affect the service strength
D. The shell shall be subject to hydrostatic test according to the specified pressure and can be used only after passing the test
E. The flame retardant layer of corrugated structure shall be processed with steel strip, which shall be bright and free of rust and oil stain
F. The fire retardant layer shall be tightly wound into a whole without loosening, and the surface of the fire retardant layer shall be flat, smooth and free of burrs
G. The pore size on the fire retardant layer shall be completely uniform without blockage to ensure that each pore is unblocked
H. The fire retardant layer shall be installed in the shell without shaking, the contact surface shall be closely connected, and there shall be no pores around
1. After assembly, the flame arrester shall be tested for fire resistance performance according to regulations
The flame retardant layer thickness and ripple height of corrugated flame arrester can be classified according to different gases
Gas classification | Ⅰ | ⅡA | ⅡB | ⅡC |
Ripple height / mm | 1.13 | 0.61 | 0.61 | 0.43 |
Thickness of fire retardant layer / mm | 38 | 19 | 38 | 76 |
The effective area of corrugated pores on the flame retardant layer of corrugated flame arrester should account for about 80% ~ 90% of the total flow area of flame arrester Generally not less than 80% Because the effective area directly affects the performance of the flame arrester, and the thickness of the material selected for the flame retardant layer also directly affects the intersection area of the flame retardant layer Therefore, in any case, the selection of material thickness shall meet the needs of manufacturing and processing, and can be processed and formed. At the same time, the nature of the material and the environmental conditions of use shall be considered